[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023652":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023652,751,1,"单选题","某电厂新建两台135MW燃煤发电机组，电厂以220kV电压接入系统，出线2回,预留1回。两台机组均采用发电机一变压器组单元接线接入厂内220kV母线。发电机引出线及厂用分支线采用分相封闭母线。 已知IA段计算负荷为13520kVA,IB段计算负荷13160kV A，其中重复容量为8177kVA。电动给水泵电机效率为η=90%，cosφ=O.963,启动电流倍数为6.5，试计算髙压厂用变压器供电时给水泵电动机正常启动时的母线电压（标么值）为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.856；",true,{"key":16,"text":17,"correct":18},"B","0.863；",false,{"key":20,"text":21,"correct":18},"C","0.869；",{"key":23,"text":24,"correct":18},"D","0.874.","解答过程： 根据DL\u002FT5153—2002附录J的有关公式。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]