[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023649":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023649,751,1,"单选题","某电厂新建两台135MW燃煤发电机组，电厂以220kV电压接入系统，出线2回,预留1回。两台机组均采用发电机一变压器组单元接线接入厂内220kV母线。发电机引出线及厂用分支线采用分相封闭母线。 初步拟定的电气主接线如图6所示，请指出图中存在的问题（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","不宜设置专用旁路断路器；220kV母线避雷器不应装设隔离开关，厂用分支戏不应装设隔离开关；",false,{"key":16,"text":17,"correct":14},"B","不宜设置专用旁路断路器；220kV母线避雷器不应装设隔离开关，厂用分支线不应装设隔离开关；",{"key":19,"text":20,"correct":21},"C","不宜设置旁路母线；母线避雷器和母线电压互感器宜合用一杻隱离开关，出线电压互感器不应装设隔离开关；厂用分支线不应装设隔离开关；变压器220kV侧中性点应装设间隙；",true,{"key":23,"text":24,"correct":14},"D","不宜设至旁路母线，母钱避雷器和母线电压互感器宜合用一組隔离开关，厂用分支线不应装设隔离开关，变压器220kV侧中性点不应装设隔离开关。","解答过程： 根据《火力发电厂设计技术规程》（DL\u002FT5000—2000）第13.2.6条220kV及以下母线避雷器和电压互感器宜合用一组隔离开关；13.2.11条当断路器为六氟化硫型时，不宜设 旁路设施；13.3.8条当厂用分支线采用分相封闭母线时不应装设断路器和隔离开关。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]