[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023648":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1023648,751,1,"单选题","已知最大接地短路电流（500kV主母线单相接地短路）：Imax=26.58kA （参数同25题），假定短路时4台主变压器中性点均接地运行，短路的等效持续时间为0.6s。Ke1、Ke2分别为厂内和厂外短路时，避雷线的工频分流系数，分别取值为0.5和0.1。 已知土壤电阻率ρ=15OΩ?m,接地网总面积S=250000m2，假定接地网采用60X6镀锌扁钢、按1OmX1Om方孔铺设，均压带计算根数n=50，埋深h=8m，接地装置的接地电阻R=0.12Ω,通过计算确定接地网内接触电位差是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","181.8V,满足要求；",false,{"key":16,"text":17,"correct":14},"B","193.14V,满足要求；",{"key":19,"text":20,"correct":14},"C","205.56V,满足要求；",{"key":22,"text":23,"correct":24},"D","248.76V,满足要求。",true,"解答过程： 根据DL\u002FT621—1997附录B及3.4节有关公式。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]