[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023647":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023647,751,1,"单选题","已知最大接地短路电流（500kV主母线单相接地短路）：Imax=26.58kA （参数同25题），假定短路时4台主变压器中性点均接地运行，短路的等效持续时间为0.6s。Ke1、Ke2分别为厂内和厂外短路时，避雷线的工频分流系数，分别取值为0.5和0.1。 假定接地线采用热浸镀锌扁钢，试计算热稳定要求的接地线最小截面为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","98.04mm2；",false,{"key":16,"text":17,"correct":14},"B","118.73mm2；",{"key":19,"text":20,"correct":21},"C","152.93mm2；",true,{"key":23,"text":24,"correct":14},"D","294.13mm2。","解答过程： 根据《交流电气装置的接地》（DL\u002FT621—1997）附录C。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]