[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023646":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023646,751,1,"单选题","已知最大接地短路电流（500kV主母线单相接地短路）：Imax=26.58kA （参数同25题），假定短路时4台主变压器中性点均接地运行，短路的等效持续时间为0.6s。Ke1、Ke2分别为厂内和厂外短路时，避雷线的工频分流系数，分别取值为0.5和0.1。 试计算入地短路电流为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","10.10kA；",false,{"key":16,"text":17,"correct":18},"B","13.82kA；",true,{"key":20,"text":21,"correct":14},"C","10.73kA；",{"key":23,"text":24,"correct":14},"D","11.42kA。","解答过程： 根据《电力工程电气设计手册》（1）120~121页及920页的有关公式：",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]