[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023643":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023643,751,1,"单选题","某市电力调度楼需设置一套火灾自动报警系统。请确定： 如控制室面积为8X1Om2,房间高度5m,屋顶平吊顶，室内应布置火灾探测器的数量为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","3；",false,{"key":16,"text":17,"correct":18},"B","4；",true,{"key":20,"text":21,"correct":14},"C","5；",{"key":23,"text":24,"correct":14},"D","6。","解答过程： 根据GB50116—1998第8.1.4条有关规定， N=S\u002F（KXA）=8X10\u002F（1.0X20）=4（只） 式中N——探测器数量（只，N取整数） S——该探测区面积（m2） A——测器保护面积（m2）（本题取20） K——修正系数，二级保护对象取0.9~1.0 可判断B正确。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]