[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023640":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023640,751,1,"单选题","某电厂新建4X300MW国产亚临界燃煤发电机组，以500kV升高电压接入系统，500kV出线2回，500kV出线及母线均不装设高压并联电抗器。4台机组连续建设，均采用发电机一变压器组单元接线接入厂内5OOkV每线，该电厂是区域性主力电源，在系统中具有十分重要的地位。取基准容量Sj=1OOMVA,500kV系统正、负序电抗为0.006,零序阻抗为0.013；主变压器370MVA,Ud=14%,零序阻抗105.1Ω；发电机额定功率3OOMW，最大连续功率33OMW,直轴超瞬变电抗（饱和值）X\"d=16%,负序电抗（饱和值）X2=17.18%，零序电抗（饱和值）X0=7.3%，cosφ=0.85,出口电压为20kV。主保护动作时间加相应断路器开断时间为0.1s,后备保护动作时间加相应断路器开断时间为1s。 已知短路电流热效应计算时间取Is时，短路电流热效应Qt0.1=68.24kA2?S,t=1s时，Qt1=440.92kA2?S,假定500kV母线三相短路电流周期分量起始有效值为24.32kA,单相短路电流值为25.40kA。请在下列数据中选择一组作为500kV断路器选择的技术条件（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1s热稳定电流 20.10kA,額定开断电流 24.32kA；",false,{"key":16,"text":17,"correct":14},"B","1s热稳定电流 20.10kA,额定开断电流 25.40kA；",{"key":19,"text":20,"correct":21},"C","2s热稳定电流 14.85kA,額定开断电流 24.32kA；",true,{"key":23,"text":24,"correct":14},"D","2s热稳定电流 14.85kA,额定开断电流 25.40kA。","解答过程： 根据《导体和电器选择设计技术规定》（DL\u002FT5222—2005）。 1）按第9.2.4条规定，持续时间为2s。 2） 2s热稳定电流计算 3）按第9. 2.16条规定，所选断路器额定开断电流应不小于最大短路电流。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]