[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023638":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023638,751,1,"单选题","某电厂新建4X300MW国产亚临界燃煤发电机组，以500kV升高电压接入系统，500kV出线2回，500kV出线及母线均不装设高压并联电抗器。4台机组连续建设，均采用发电机一变压器组单元接线接人厂内5OOkV每线，该电厂是区域性主力电源，在系统中具有十分重要的地位。取基准容量Sj=1OOMVA,500kV系统正、负序电抗为0.006,零序阻抗为0.013；主变压器370MVA,Ud=14%,零序阻抗105.1Ω；发电机额定功率3OOMW，最大连续功率33OMW,直轴超瞬变电抗（饱和值）X\"d=16%,负序电抗（饱和值）X2=17.18%，零序电抗（饱和值）X0=7.3%，cosφ=0.85,出口电压为20kV。主保护动作时间加相应断路器开断时间为0.1s,后备保护动作时间加相应断路器开断时间为1s。 试计算500kV母线单相短路电流起始有效值为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","8.46kA；",false,{"key":16,"text":17,"correct":18},"B","25.38kA；",true,{"key":20,"text":21,"correct":14},"C","7.33kA；",{"key":23,"text":24,"correct":14},"D","21.99kA。","①根据正序网络图计算X1Σ=O. 004； ②根据负序网络图计算X2Σ=O.004； ③根据零序网络图计算X0Σ=0.005；",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]