[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023634":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1023634,751,1,"单选题","某300MW机组火力发电工程，主厂房设两台工作变压器，容量互为备用，设一段电动机控制中心（MC C）,变压器中性点直接接地?选择柴油发电机组时，事故保安A段计算负荷为435kVA,B段计算负荷为430kV A，重复计算负荷300kVA。接于PC和MCC的电负荷资料及厂用电接线见图5。 假定本案例中低压工作变容量为1000kVA。排水泵电动机回路接于MC C，选用塑壳断路器作为保护设备，电缆采用铝芯3X6mm截面，长度50m。已知MCC盘母线三相短路电流11kA,单相短路电流4.5kA；电动机出口三相短路电流0.99k A，单相短路电流0.5kA。排水系电动机回路不另装设继电保护，则过电流脱扣器的整定电流为（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","7300A；",false,{"key":16,"text":17,"correct":14},"B","660A；",{"key":19,"text":20,"correct":14},"C","3000A；",{"key":22,"text":23,"correct":24},"D","300A。",true,"解答过程：根据DL\u002FT 5153—2002附录Q，断路器过电流脱扣器的整定电流应按下式计算：Iz≤I\u002F1.5（1.5为灵敏系数）=500\u002F1.5=333.33A,取300A。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]