[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023632":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023632,751,1,"单选题","某300MW机组火力发电工程，主厂房设两台工作变压器，容量互为备用，设一段电动机控制中心（MC C）,变压器中性点直接接地?选择柴油发电机组时，事故保安A段计算负荷为435kVA,B段计算负荷为430kV A，重复计算负荷300kVA。接于PC和MCC的电负荷资料及厂用电接线见图5。 选择低压工作变容量时，其计算负荷应为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","655.375kVA；",true,{"key":16,"text":17,"correct":18},"B","731.25kVA；",false,{"key":20,"text":21,"correct":18},"C","762.75kVA；",{"key":23,"text":24,"correct":18},"D","632.75kVA。","解答过程： 根据DL\u002FT5153—2002附录D计算。注意热控配电箱计入保安段后，PC段不应再计算，同时注意保安段计算时换算系数取0.8，而选变压器时换算系数应取0.7。 计算过程：Se=（110+75+30+12+3）X0.7+（435+430-300）X0.7\u002F0.8=655.375（kVA）",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]