[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023630":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023630,751,1,"单选题","某300MW机组火力发电工程，主厂房设两台工作变压器，容量互为备用，设一段电动机控制中心（MC C）,变压器中性点直接接地?选择柴油发电机组时，事故保安A段计算负荷为435kVA,B段计算负荷为430kV A，重复计算负荷300kVA。接于PC和MCC的电负荷资料及厂用电接线见图5。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","如不考虑供电距离的影响， MCC盘上的计算负荷至多为（）。",true,{"key":16,"text":17,"correct":18},"B","31.5kVA；",false,{"key":20,"text":21,"correct":18},"C","33.25kVA；C36.75kVA；",{"key":23,"text":24,"correct":18},"D","64.75kVA?","解答过程： 根据DL\u002FT5153—2002第4.7.5条第2款规定，75kW及以上的电动机宜由PC盘供电，根据第4.7.10条规定，热控配电箱应由PC盘供电，又根据第5.1.1条规定，不经常而短时运行的设备不予计算，电动葫芦虽接于MCC，但不计算负荷，故Se=（30+12+3）X0.7=31.5（kVA）?",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]