[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023616":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023616,751,1,"单选题","某500kV变电站的主变压器型式为：三相油浸自耦变压器，无载调压，冷却方式为强油风冷。主要技术参数为： 电流互感器额定二次电流：三侧均为1A。 按双重化配置微机型变压器保护。 假定变压器过负荷保护接于准确级次为5P20的电流互感器，下列关于5P20误差限值的描述中，正确的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","一次短路电流为額定电流20倍时比值谡差不大于5%；",false,{"key":16,"text":17,"correct":14},"B","一次短路电流为額定电流20倍时相角误差不大于5%；",{"key":19,"text":20,"correct":21},"C","一次短路电流为額定电流20倍时复合误差不大于5%；",true,{"key":23,"text":24,"correct":14},"D","—次短路电流为額定电流5倍时复合误差不大于20%。","解答过程： 根据电力工程电气设计手册（电气二次部分）表20-13（64页）可判断C正确。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]