[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023614":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023614,751,1,"单选题","某500kV变电站的主变压器型式为：三相油浸自耦变压器，无载调压，冷却方式为强油风冷。主要技术参数为： 电流互感器额定二次电流：三侧均为1A。 按双重化配置微机型变压器保护。 假定：Ie为变压器高压侧二次额定电流，Kk为可靠系数（取1.5）, Kct为电流互感器变比误差系数（取0.1），Kb为变压器调压误差系数（取0.1）。则该主变压器差动保护 动作电流定值Icd=（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","0.1Ie；",false,{"key":16,"text":17,"correct":14},"B","O.2Ie；",{"key":19,"text":20,"correct":21},"C","O.3Ie；",true,{"key":23,"text":24,"correct":14},"D","0.4Ie。","解答过程： 根据DL\u002FT684-19905.1.3.3款中a），1）“纵差保护最小动作电流的整定”：",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]