[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023613":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023613,751,1,"单选题","某500kV变电站的主变压器型式为：三相油浸自耦变压器，无载调压，冷却方式为强油风冷。主要技术参数为： 电流互感器额定二次电流：三侧均为1A。 按双重化配置微机型变压器保护。 变压器差动保护动作电流定值的整定计算原则是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","按躲过变压器额定运行时最大不平衡电流整定；",false,{"key":16,"text":17,"correct":18},"B","按躲过变压器外部短路时最大不平衡电流整定；",true,{"key":20,"text":21,"correct":14},"C","按躲过变压器励磁涌流整定；",{"key":23,"text":24,"correct":14},"D","按躲过变压器运行时最大负荷电流整定，","解答过程： 根据DL\u002FT684—19905.1.3.2款中有关规定，可判断B正确，",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]