[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023609":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023609,751,1,"单选题","某变电站的35kV断路器采用三相联动电气操动机构，电气防跳采用电流启动电压保持的“串联防跳”接线方式，该断路器控制电压为220VD C，合闸电流为2 A，跳闸电流为1A。 防跳继电器的参数应选（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","220V，0.5A；",true,{"key":16,"text":17,"correct":18},"B","220V,1A；",false,{"key":20,"text":21,"correct":18},"C","220V,2A；",{"key":23,"text":24,"correct":18},"D","110V,1A。","解答过程： 根据《电力工程电气设计手册》（2）20-7节（耵页）“防跳继电器电流线闽额定电流与断路器跳闸电流配合，并要求动作的灵敏系数不小于1.5；自保持电压线圈按额定电压选择”。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]