[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023607":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023607,751,1,"单选题","某变电站的35kV断路器采用三相联动电气操动机构，电气防跳采用电流启动电压保持的“串联防跳”接线方式，该断路器控制电压为220VD C，合闸电流为2 A，跳闸电流为1A。 下列关于断路器控制回路设计要求的描述中，不正确的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","应有控制回路电源监视，并宜监视跌、合闸回路完整性；",false,{"key":16,"text":17,"correct":14},"B","断路器合闸或跳闸完成后应使命令路冲自动解除；",{"key":19,"text":20,"correct":21},"C","断路器合闸和跳闸回路的电源应由两回不同的直流电源分别供电；",true,{"key":23,"text":24,"correct":14},"D","应有防止断路器出现“跳跃”现象的电气闭锁装置。","解答过程： 根据“火力发电厂、变电所二次接线设计技术规程”（DL\u002FT5136-2001）7.1.2条的相关规定。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]