[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023602":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023602,751,1,"单选题","某变电站的500kV线路为关口计量点，拟装设专门的0.2级计费电能表，线路电流互感器和电压互感器均设有专门的计量用二次绕组。其中，线路电压互感器为三相星形接线，电压互感器一次电压为500A\u002F√3kV，二次星形电压为0.1\u002F√3kV。 下列关于电能量计量表计接线的描述中，不正确的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","当电能量计量表计与测量仪表共用电流互感器二次绕组时，电能量计量表计应接入电流互感器二次回路的最前端；",false,{"key":16,"text":17,"correct":18},"B","电能量计量表计专用电压互感器二次回路需装设隔离开关辅助触点；",true,{"key":20,"text":21,"correct":14},"C","主接线为双母线电压互感器切换时，两个电压互感器二次回路之间不应有公共电缆线；",{"key":23,"text":24,"correct":14},"D","当旁路断路器不代路时，旁路回路的远方电能量计量表计电压亙感器二次输入信号应断开。","解答过程： 根据《电能量计量系统设计技术规程》（DL\u002FT5202—2004）第8章“二次回路”的相关规定，可判断答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]