[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023581":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023581,751,1,"单选题","某新建2X300MW火力发电厂，每台机组设 A、B两段6kV工作段，全厂设01 A、O1B两段6kV公用段，公用段间设有联络断路器，正常运行时公用段分别由I A、IIA单元段供电。每台机组设一台分裂绕组髙压工作变压器，容量50\u002F27-27MV A，半穿越阻抗U’ dl-2=21%,额定变比20±2X2.5%\u002F6.3—6.3kV。每台机组设一台备用电动给水泵，接于单元B段。发电机出口短路容量为4330MV A，每段6kV母线计算负荷及所接电动机额定功率之和如表3所示。 若电动机平均的反馈电流倍数取6，则高厂变供电时，6kV真空断路器柜较合理的热稳定电流应选择（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","40kA（2S）；",false,{"key":16,"text":17,"correct":14},"B","50kA（2S）；",{"key":19,"text":20,"correct":21},"C","40kA（4S）；",true,{"key":23,"text":24,"correct":14},"D","50kA（4S）。","解答过程： 短路电流计算应按可能的最大运行方式，电动机额定功率之和最大的是IB段，即11860kW。 根据《火力发电厂厂用电设计技术规定》（DL\u002FT5153—2002）附录M中的计算方法计算，",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]