[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023579":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023579,751,1,"单选题","某电厂装设4X300MW机组，有220kV及500kV升髙电压，电厂潮流均应向两种高压送电，其中1、2号机组接入220kV母线，3、4号机组接人500kV母线。220kV出线两回，500kV出线一回。 每台机组总的计算负荷为35500kV A，则髙厂变的型式及台数宜采用（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","—台双绕组变压器，两段6kV母线；",false,{"key":16,"text":17,"correct":18},"B","一台分裂绕组变压器，两段6kV母线；",true,{"key":20,"text":21,"correct":14},"C","两台双绕组变压器，两段6kV母线；",{"key":23,"text":24,"correct":14},"D","两台分裂統组变压器，四段6kV母线，","解答过程： 根据DL\u002FT5000—2000第13.3.12条规定，200~300MW机组的高压厂用工作电源宜采用一台分裂绕组变压器，及第13.3.16条规定，锅炉容量为400t\u002Fh以上时，每台锅炉每—级高压厂用电压应不少于两段母线。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]