[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023576":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023576,751,1,"单选题","某110kV降压变电站，规划安装两台双绕组主变压器，10kV负荷容量20000kVA,出线14回，110kV出线为2回。110kV配电装置采用SF6断路器，10kV配电装置采用手车式开关柜，10kV负荷均为一级负荷。 假定10kV母线0秒时三相短路电流33k A，每段10kV母线装设4组电容器，电容器组电抗率采用6%，较适宜的单组电容器容量为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1200kvar；",true,{"key":16,"text":17,"correct":18},"B","2400kvar；",false,{"key":20,"text":21,"correct":18},"C","3600kvar；",{"key":23,"text":24,"correct":18},"D","4800kvar。","解答过程： 根据《并联电容器装置设计规范》（GB50227—1995）第3.0.2条规定，电容器安装可按变压器容量的10%~30%，即最大为20000X30%=6000kvar。按第3.0.3条计算，三次谐波谐振电容器容量为： 从计算结果看，谐振电容器容量不是控制条件，6000kvar分为4组后，最适宜的容量应为1200kvar。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]