[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023575":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023575,751,1,"单选题","某110kV降压变电站，规划安装两台双绕组主变压器，10kV负荷容量20000kVA,出线14回，110kV出线为2回。110kV配电装置采用SF6断路器，10kV配电装置采用手车式开关柜，10kV负荷均为一级负荷。 假定10kV母线（电缆）单相接地故障电流为28. 5 A，则主变压器10k公侧中性点接地方式为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","不接地；",true,{"key":16,"text":17,"correct":18},"B","消弧线圏接地；",false,{"key":20,"text":21,"correct":18},"C","直地；",{"key":23,"text":24,"correct":18},"D","高电阻接地。","解答过程： 根据DL\u002FT620—1997第3.1.2条，对3~10kV不直接连接发电机的系统，当单相接地电容电流不超过30A时，应采用不接地。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]