[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023556":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023556,751,1,"单选题","某500kV变电站装设2组750MVA主变压器，三级电压为：500、220、35kV,站用负荷统计为：P1动力负荷536kW，其中包括深井水泵20kW、生活水泵5kW和消防泵80kW,P2空调和电热负荷1OOkW；P3照明负荷80kW。 关于站用变型式和阻抗选择，下面说法中错误的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","站用电低压系统应采取防止变压器并联运行的措施；",false,{"key":16,"text":17,"correct":14},"B","站用变压器阻抗应按低压电器对短路电流的承受能力确定，宜采用标准系列的普通变压器。",{"key":19,"text":20,"correct":21},"C","站用变压器的联结组应采用Yynll；",true,{"key":23,"text":24,"correct":14},"D","当高压例电压波动大，经常使站用母线电压偏移超过5%时，应采用有载调压变压器。","解答过程：根据《220kV~500kV变电所所用电设计技术规》（DL\u002FT 5155—2002） 第5.2节中相关规定，答案中仅C不正确，其余均正确。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]