[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023555":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023555,751,1,"单选题","某500kV变电站装设2组750MVA主变压器，三级电压为：500、220、35kV,站用负荷统计为：P1动力负荷536kW，其中包括深井水泵20kW、生活水泵5kW和消防泵80kW,P2空调和电热负荷1OOkW；P3照明负荷80kW。 下面关于站用电的说明正确的是（），",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","为了保证站用电的可靠性，2台工作站用变压器应并联运行；",false,{"key":16,"text":17,"correct":18},"B","站用变压器的接线组别宜采用Dynll；",true,{"key":20,"text":21,"correct":14},"C","对重要站用负荷应分别接于两段母线上，单回路供电；",{"key":23,"text":24,"correct":14},"D","消防泵为重要负荷，在站用变容量选择时，统计负荷应计入动力负荷中。","解答过程：根据DL\u002FT 5155—2002第4章和第5章中相关规定，仅答案B正确，其余均不正确。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]