[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023552":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023552,751,1,"单选题","某110kV变电站，位于城镇郊外，装设40MVA主变压器2台，三级电压为110kV\u002F35kV\u002F10kV；110kV出线2回，线路较长并穿过多雷山区，事故多发，线路无穿越功率；35kV出线6回；1OkV出线10回；各级电压短路电流水平为：110kV为25k A、35kV为20k A、1OkV为16kA；无功补偿电容器组装设于10kV，补偿容量按主变压器容量的20%,电网背景谐波为5次及以上。 现有库存电容器，额定电压为11kV,额定容量334kvar，用于上述10kV电容器组时，下面设想正确的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","采用单星形接线，但输出容量要降低；",true,{"key":16,"text":17,"correct":18},"B","采用三角形接线，输出容量不会降低；",false,{"key":20,"text":21,"correct":18},"C","采用桥形接线；",{"key":23,"text":24,"correct":18},"D","采用单星形接线和相电压差动保护。","解答过程：根据GB 50227—1995的相关规定，电容器组的接线方式为星形接线，10kV电容器组可能采用的电容器额定电压为11\u002F√3kV（电抗率K=5%），额定电压为11kV的电容器，采用单星形接线，运行电压降低了，输出容量因而会降低。所以选择答案A。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]