[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023551":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023551,751,1,"单选题","某110kV变电站，位于城镇郊外，装设40MVA主变压器2台，三级电压为110kV\u002F35kV\u002F10kV；110kV出线2回，线路较长并穿过多雷山区，事故多发，线路无穿越功率；35kV出线6回；1OkV出线10回；各级电压短路电流水平为：110kV为25k A、35kV为20k A、1OkV为16kA；无功补偿电容器组装设于10kV，补偿容量按主变压器容量的20%,电网背景谐波为5次及以上。 下面关于并联电容器装置设计的说明正确的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","电容器组应采用三角形接线；",false,{"key":16,"text":17,"correct":14},"B","由于并联电容器装置回路装设了串联电抗器，因此，电容器组电压比母线电压低；",{"key":19,"text":20,"correct":21},"C","电容器组的每相或每个桥臂，由多台电容器组舍连接时，应采用先并联后串联的接线方式；",true,{"key":23,"text":24,"correct":14},"D","并联电容器装置应设置重合闸装置，以保证跌闸后快速投入不间断无功供应。","解答过程：根据GB 50227—1995的4.1.2.2相关规定，除了答案C正确，其余答案均不正确。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]