[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023548":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023548,751,1,"单选题","某110kV变电站，位于城镇郊外，装设40MVA主变压器2台，三级电压为110kV\u002F35kV\u002F10kV；110kV出线2回，线路较长并穿过多雷山区，事故多发，线路无穿越功率；35kV出线6回；1OkV出线10回；各级电压短路电流水平为：110kV为25k A、35kV为20k A、1OkV为16kA；无功补偿电容器组装设于10kV，补偿容量按主变压器容量的20%,电网背景谐波为5次及以上。 每台主变压器下10kV电容器组的容量为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1X6000kvar；",false,{"key":16,"text":17,"correct":14},"B","2X3000kvar；",{"key":19,"text":20,"correct":21},"C","2X4000kvar；",true,{"key":23,"text":24,"correct":14},"D","2X5000kvar。","解答过程：电容器组的装设容量按题意为：Q=40000X20%=8000 (kvar）,如果不分组，单组容量8000Kvar对110kV变电站来说太大，一般分成两组装设。所以答案选择C。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]