[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023547":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023547,751,1,"单选题","某110kV变电站，位于城镇郊外，装设40MVA主变压器2台，三级电压为110kV\u002F35kV\u002F10kV；110kV出线2回，线路较长并穿过多雷山区，事故多发，线路无穿越功率；35kV出线6回；1OkV出线10回；各级电压短路电流水平为：110kV为25k A、35kV为20k A、1OkV为16kA；无功补偿电容器组装设于10kV，补偿容量按主变压器容量的20%,电网背景谐波为5次及以上。 根据特性和工程实践，各级电压适用的接线型式应为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","110kV单母线\u002F35kV双母线\u002F1OkV单母线分段；",false,{"key":16,"text":17,"correct":14},"B","110kV单母线\u002F35kV单母线分段\u002F1OkV双母线；",{"key":19,"text":20,"correct":21},"C","110kV内桥接线\u002F35kV单母线分段\u002F1OkV单母线分段；",true,{"key":23,"text":24,"correct":14},"D","110kV外桥接线\u002F35kV单母线\u002F1OkV单母线分段。","解答过程：110kV仅两回线，可能的接线方式是t单母线和桥接线，根据线路特性情况，适用的接线应为内桥接线；35kV和10kV根据出线回路数，比较适合的接线方式均为单母线分段接线方式。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]