[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023545":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023545,751,1,"单选题","某500kV变电站已知系统阻抗和变压器参数如图4所示，站址位于一块荒地上，围墙外面有水塘。 若变电站接地网的接地电阻实测值为0.5Ω，接地电阻值未达到0.11Ω目标要求值，需要采取措施降阻，试分析以下降阻措施可行的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","因为围墙外有水塘，可采用引外接地网；",true,{"key":16,"text":17,"correct":18},"B","扩大接地网面积到围墙外2m变电站的征地红线范围内",false,{"key":20,"text":21,"correct":18},"C","在地网中心地带设里深井接地极；",{"key":23,"text":24,"correct":18},"D","在地网内増加打入2.5m短垂直接地极。","答案分析：根据变电站的条件：扩大接地网面积到围墙外2m变电站的征地红线范围内，接地网已经出了围墙，运行安全性差；在地网中心地带设置深井接地极，投资大，效果不好；在地网内增加打人2.5m短垂直接地极，效果差，所以选择答案A。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]