[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023513":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023513,751,1,"单选题","某发电厂过电压保护及绝缘配合的设计中。 电厂送出电压为110kV,共4回线路，均为同塔双回，线路长度5km，全线设有避雷线。110kV配电装置仅设置有母线避雷器，采用金屑氧化物避雷器，所有电气设备均为标准绝缘水平，试确定母线避雷器与出线隔离开关的最大电气距离应为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","170m；",false,{"key":16,"text":17,"correct":14},"B","229.5m；",{"key":19,"text":20,"correct":21},"C","230m；",true,{"key":23,"text":24,"correct":14},"D","310.5m。","解答过程： 根据《交流电气装置的过电压保护和绝缘配合》（DL\u002FT620~1997）第7.3.4节规定，同塔双回线路只能当成1回，进线段长度按2km,査表12可得与主变压器距离最大值为170m。 与隔离开关的最大距离可增加35%,即170X1.35=229.5m。故选择答案C。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]