[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023511":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023511,751,1,"单选题","某发电厂过电压保护及绝缘配合的设计中。 以3支等高避雷针保护燃油罐区，假定针高30m，被保护物高度为7m，为使保护面积最大，避雷针向距的最大值宜取（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","161m；",false,{"key":16,"text":17,"correct":18},"B","150m；",true,{"key":20,"text":21,"correct":14},"C","210m；",{"key":23,"text":24,"correct":14},"D","159m。","解答过程： 计算依据《交流电气装置的过电压保护和绝缘配合》（DL\u002FT620—1997〉第5章。 避雷针联合保护，如在三角形内被保护物最大高度hx水平面上，各相邻避雷针间保护范围的一侧最小宽度bx≥0时，则全部面积受到保护。 实际上两针间保护范围上部边缘最低点高度h0=h—D\u002F7P≥7，则bx≥0，三角形内全部面积受到保护，由此可得：D≤7P（h—7）=7（30-7）=161（m） 但D\u002Fh不宜大于5，即D值不宜大于150m。故选择B。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]