[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023507":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023507,751,1,"单选题","某电厂为220kV送出，220kV单相短路电流最大，为46.449kA,此时入地短路电流为28.345k A，短路的等效持续时间为0.2s，接地网为复合接地网，水平接地极为镀锌扁钢，垂直接地极为50X50X5的角钢。厂区土壤比较潮湿。 接地网总面积：S=406010m2, 水平接地体埋深：h=1.Om； 接地网边缘边线总长：L0=3820m； 水平接地体总长：L=22900m, 雷季中无雨水时，实测土壤电阻率：ρ0=55.4Ω?m； 季节系数为1.2~1.45，土壤较银时取大值； 地网设计寿命30年。 该接地网的接地电阻值是（）（以简化公式计算）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","0.043Ω；",false,{"key":16,"text":17,"correct":14},"B","0.054Ω；",{"key":19,"text":20,"correct":21},"C","0.063Ω；",true,{"key":23,"text":24,"correct":14},"D","0.071Ω。","解答过程： 土壤电阻率应考虑季节系数，季节系数取1.45。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]