[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023498":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023498,751,1,"单选题","某火力发电厂电气主接线如图2所示。 为节约线路走廊，出线1和出线2为同塔双回送出，出线3和出线4也为同塔双回送出。 配电装置采用屋外敞开式普通中型配电装置，断路器单列式布置，间隔宽度15m，母线采用支持式铝管母线，管母外径150mm，两组母线间距为5m。 发电机额定容量均为300MW，最大连续容量为395MV A，母线穿越容量为800MVA。 220kV最大短路电流为40k A，短路切除时间为0.3s.每台机厂用负荷为32MVA。 如220kV主接线更改为断路器接线，所有进出线均不装进出线隔离开关，则220kV主接线中需要（）组隔离开关。所有隔离开关均为双柱水平断口型。并绘制出接线示意图，图中应画出母线、断路器、隔离开关、电流互感器、电压互感器及避雷器。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","20；",false,{"key":16,"text":17,"correct":14},"B","22；",{"key":19,"text":20,"correct":21},"C","24；",true,{"key":23,"text":24,"correct":14},"D","27。","采用1（1\u002F2）断路器接线时，共配成3个完整串及1个不完整串，共11台断路器，共需22组隔离开关，另母线电压互感器还需要2组隔离开关，共计24组。接线示意如下。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]