[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023497":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023497,751,1,"单选题","某火力发电厂电气主接线如图2所示。 为节约线路走廊，出线1和出线2为同塔双回送出，出线3和出线4也为同塔双回送出。 配电装置采用屋外敞开式普通中型配电装置，断路器单列式布置，间隔宽度15m，母线采用支持式铝管母线，管母外径150mm，两组母线间距为5m。 发电机额定容量均为300MW，最大连续容量为395MV A，母线穿越容量为800MVA。 220kV最大短路电流为40k A，短路切除时间为0.3s.每台机厂用负荷为32MVA。 图2中隔离开关的配置错误的有（）处。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","3；",false,{"key":16,"text":17,"correct":18},"B","4；",true,{"key":20,"text":21,"correct":14},"C","7；",{"key":23,"text":24,"correct":14},"D","10。","断路器双侧应配隔离开关。但变压器回路，当断路器断开检修时，变压器停运，故断路器变压器一侧也可不配隔离开关。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]