[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023494":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023494,751,1,"单选题","某300MW机组6kV设 A、B两段，分别接有电动机总功率17900、22300kW,其中I类电动机容量占80%。电动给水泵为5000kW，给水泵启动前厂用母线已带负荷S1为18000kVA,给水泵参数：启动电流倍数K Q=6，额定效率如=0.97，额定功率因数cosφ=0.9；高压厂用变压器参数：容量40\u002F25—25MV A，电压20±2X2.5%\u002F6.3—6.3kV。厂用电选择开断水平40k A、动稳定1OOkA的标准开关设备，并配置有效的快速切换装置，高压厂用变压器髙压侧按无穷大电源系统考虑，试确定高压厂用变压器的半穿越电抗X DL-2’ %的取值，开断水平按Os计算。 髙压厂用变压器的半穿越电抗X DL-2’ %最小可取为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","10.5；",false,{"key":16,"text":17,"correct":14},"B","17.02；",{"key":19,"text":20,"correct":21},"C","18.53；",true,{"key":23,"text":24,"correct":14},"D","20.13。","解答过程： 根据《火力发电厂厂用电设计技术规定》（DL\u002FT5153—2002）附录M计算。按设备选择的短路水平确定厂用变压器电抗的最小值： 按开断水平计算： 两者取大者，结论为C",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]