[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023493":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023493,751,1,"单选题","某水电厂装机容量为3X50MW,选用了3台厂用变压器，且互为备用，发电机电压无直配线。 如发电机单机容量为150MW,发电机内部发生单相接地故瘅不要求瞬时切机。经计算，发电机电压回路及升压变压器低压卷的电容电流总计为2.5 A，发电机中性点宜采用的接地方式为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","中性点不接地；",false,{"key":16,"text":17,"correct":14},"B","中性点直接接地；",{"key":19,"text":20,"correct":21},"C","中性点经消弧线圈接地（欠补偿方式）；",true,{"key":23,"text":24,"correct":14},"D","中性点经消弧线圈接地（过补偿方式）。","解答过程： 根据《交流电气装置的过电压保护和绝缘配合》DL\u002FT620—1997第3.1.3条应为C。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]