[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023492":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1023492,751,1,"单选题","某水电厂装机容量为3X50MW,选用了3台厂用变压器，且互为备用，发电机电压无直配线。 上述调速油泵电机启动时间约8s,其供电回路设计时采用RTO型熔断器作短路保护，电机的启动电流倍数为6.5,则熔件额定电流宜选择（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","80A；",false,{"key":16,"text":17,"correct":14},"B","100A；",{"key":19,"text":20,"correct":14},"C","200A；",{"key":22,"text":23,"correct":24},"D","250A。",true,"解答过程： IQ=6.5X68.2=443.3（A） IQ≥IQ\u002Fα1=443.3\u002F2.5=177.3（A），公式及α1取值参照《火力发电厂厂用电设计技术规定》（DL\u002FT5153—2002）附录Q。 由于电机启动时间为8s，计算的溶件还需要放大一级，故选D。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]