[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023490":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023490,751,1,"单选题","某水电厂装机容量为3X50MW,选用了3台厂用变压器，且互为备用，发电机电压无直配线。 所有同时运行的最大负荷的额定功率总和为1233kW；厂用电负荷的综合系数取0.75,则厂用变压器容量选（）最合适。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","315kVA；",false,{"key":16,"text":17,"correct":14},"B","400kVA；",{"key":19,"text":20,"correct":21},"C","500kVA；",true,{"key":23,"text":24,"correct":14},"D","630kVA。","解答过程： 厂用电最大负荷：Sjs=K0ΣP0=0.75X1233=924.8（kVA） 根据《水力发电厂厂用电设计规程》（DL\u002FT5153—2002）第6.2.2条： 厂用变压器容量=（0.5-0.6）X924.8=（462.4~554.9）（kVA） 厂用变压器选500kVA最合适，故C正确。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]