[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023484":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023484,751,1,"单选题","某8X125MW燃煤机组设置有燃油系统，燃油系统及邻近区域电负荷如表1,所有电机的启动电流倍数均为7,功率因数均为0.8。 以上负荷均按II类负荷。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","如表中负荷设置2台暗备用变压器供电，则每台变压器的容量宜选择（）。",false,{"key":16,"text":17,"correct":14},"B","315kVA；",{"key":19,"text":20,"correct":21},"C","400kVA； C500kVA；",true,{"key":23,"text":24,"correct":14},"D","630kVA。","解答过程： 根据《火力发电厂厂用电设计技术规定》（DL\u002FT5153-2002）5.1及附录G，选变压器容量时宜采用换算系数法，计算功率P的取值应为，经常短时的负荷P=O.5Pe，不经常短时的负荷P=0，经常连续和不经常连续的负荷P=Pe，按此计算ΣP=（90+75）X2X0.5+（55+30）X2+11X1X0.5+1.1X5+5+18.5X2+3+105=496（kW） 125MW机组换算系数取K=0.8 计算负荷S=KΣP=O.8X496=396.8（kVA） 按《火力发电厂厂用电设计技术规定》DL\u002FT5153—2002第5.2.1条规定，低压厂用变压器的容量宜留有10%的裕度，故选择C.",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]