[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023483":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023483,751,1,"单选题","某燃煤发电厂，装机容量为4X125MW，以发电机一变压器组单元接线接入220kV及110kV配电装置。220kV送出线路共4回。110kV送出线路共8回，220kV及110kV断路器选用SF6柱式断路器， 发电机的额定功率因数均为0.85。 发电机出口电压为15.75kV。厂址内最热月平均最高温度为35℃。 电厂布置中，220kV架空线与110kV架空线出现交叉，220kV在上方，110kV在下方。220kV导线与110kV线路避雷线之间的垂直距离应大于（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","2m；",false,{"key":16,"text":17,"correct":14},"B","3m；",{"key":19,"text":20,"correct":21},"C","4m；",true,{"key":23,"text":24,"correct":14},"D","3.8m。","分析过程： 根据《110~500kV架空送电线路设计技术规程》（DL\u002FT5092—1999）表16.0.10，也可参照《交流电气装置的过电压保护和绝缘配合》（DL\u002FT620—1997）表9。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]