[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023482":3},{"question":4,"library":25},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":21,"analysis":24},1023482,751,1,"单选题","某燃煤发电厂，装机容量为4X125MW，以发电机一变压器组单元接线接入220kV及110kV配电装置。220kV送出线路共4回。110kV送出线路共8回，220kV及110kV断路器选用SF6柱式断路器， 发电机的额定功率因数均为0.85。 发电机出口电压为15.75kV。厂址内最热月平均最高温度为35℃。 发电机回路的导体，经济合理的选择是（）。",[11,15,17,20],{"key":12,"text":13,"correct":14},"A","矩形铜导体4（125X10）；",false,{"key":16,"text":13,"correct":14},"B",{"key":18,"text":19,"correct":14},"C","槽形铝导体175X80X8；",{"key":21,"text":22,"correct":23},"D","槽形铝导体200X90X10。",true,"计算过程： Ig=1.05X125\u002F（√3X15.75X0.85）=5660（A） 按《导体和电器选择设计技术规定》（DL\u002FT5222—2005）第7.3.2条要求，宜选槽形导体，第6.0.2条要求，实际环境温度应取35+5=40℃,修正系数应取0.81（见表D11）。槽形铝导体200X90X10的载流量为755OX0.81=6115.5（A）",{"id":6,"name":26,"category":27,"favorite":28},"电气工程师发输变电专业","建筑工程",0]