[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023478":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023478,751,1,"单选题","某火力发电厂新建4台300MW机组，高压厂用电压采用6kV，高压厂用工作变压器选用容量为40\u002F25—25MVA的分裂变压器，其半穿越阻抗Zl dl-2'=16.5%，单侧铜耗为160kW。厂变分裂系数为3.5。 电厂输煤系统设置了两台1OOOkVA的低压干式变压器，Ud=6%,互为备用.容量为55kW的电动机回路，开关脫扣器的短路瞬动整定电流值为1800 A，未装设接地短路保护，选用3X95mm2铝芯电缆，为使回路发生短路故障时脱扣器能可靠动作，电动机距离供电中心的电气距离大约应在（）范围内。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","70m；",true,{"key":16,"text":17,"correct":18},"B","100m；",false,{"key":20,"text":21,"correct":18},"C","200m；",{"key":23,"text":24,"correct":18},"D","250m。","解答过程： 脱扣器的灵敏系数5则短路电流I\u002FIz≥1.5 则短路电流Imin=1.5X1800=2700（A）, 55kW及以上电动机应校验单相接地短路保护的灵敏度（三相短路电流要大一些，所以核单相）。 根据给出的变压器容量1OOOkVA、阻抗电压6%、电缆规格铝芯3X95，查《火力发电厂厂用电设计技术规程》（DL\u002FT5153—2002）P27，可得供电距离大约为70m。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]