[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023476":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023476,751,1,"单选题","某火力发电厂新建4台300MW机组，高压厂用电压采用6kV，高压厂用工作变压器选用容量为40\u002F25—25MVA的分裂变压器，其半穿越阻抗Zl dl-2'=16.5%，单侧铜耗为160kW。厂变分裂系数为3.5。 机组电动给水泵为6300kW，给水泵启动前厂用母线已带负荷S1为l8000kV A，给水泵参数：启动电流倍数KQ=6,额定效率ηQ=0.97,额定功率因数cosφ=0.9,那么给水泵启动时母线电压标么值应为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.82；",true,{"key":16,"text":17,"correct":18},"B","0.84；",false,{"key":20,"text":21,"correct":18},"C","0.876；",{"key":23,"text":24,"correct":18},"D","0.864。","解答过程： 根据《火力发电厂厂用电设计技术规定》（DL\u002FT5153—2002）附录J，无励磁调压变压器取1.05见附录H。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]