[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023472":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023472,751,1,"单选题","某钢铁公司自备热电厂装机3X60MW，发电机出口电压为1OkV,钢铁公司需要20回1OkV电源，多余电量以110kV电压等级上网。 1OkV出线每回容量最小为5MV A，均为电缆出线，供电距离100~2000m不等。 厂用电率按8%考虑，cosφ=0.8。 本电厂主变压器选择最合理的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1台125MVA双绕组变压器；",false,{"key":16,"text":17,"correct":14},"B","2台63MVA双绕组变压器；",{"key":19,"text":20,"correct":21},"C","2台75MVA双统组变压器；",true,{"key":23,"text":24,"correct":14},"D","2台125MVA双绕组变压器。","解答过程： 根据《火力发电厂设计规程》（DL5000~2000）13.1.4要求，60MW及以下机组的发电厂，接于发电机电压母线的主变压器不应少于2台。 对装设2台主变压器的发电厂，当1台主变压器故障时，另1台应能承担70%的容量.（根据《电力工程电气设计手册》214页所述）。 主变压器容量=（3X60\u002F0.8—20X5—3X60\u002F0.8X8%）X0.7=74.9（MVA），取2台75MVA最合理。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]