[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023462":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023462,751,1,"单选题","图17是一个500kV电网系统示意图，图中示出了3个地区电网，其中 A、B之间通过单回500kV线路连接， B、C之间通过同杆双0线连接。 为了保证 B、C电网之间的线路发生第二级安全稳定标准下的故障时电网稳定运行，应该采用下列（）故障进行校核。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","单相瞬时接地故障重合成功；",true,{"key":16,"text":17,"correct":18},"B","单相永久故障重合不成功；",false,{"key":20,"text":21,"correct":18},"C","三相故障断开不重合；",{"key":23,"text":24,"correct":18},"D","同杆双面线异名相跨线故障。","分析：根据DL 755—2001中的关于电力系统的第二级安全稳定标准的要求，发生D类故障，在采取切机切负荷措施后，电网应保持稳定。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]