[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023458":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023458,751,1,"单选题","图16是一个500kV电网图，AB线上的故障切除时间必须控制在100ms以内（含100ms）,才能保证500kV电网稳定运行。 请从图16中确定A站与B站之间的AB线路的主保护为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","距离I段保护+距离II段保护；",false,{"key":16,"text":17,"correct":14},"B","方向零序电流I段保护+方向零序电流II段保护；",{"key":19,"text":20,"correct":21},"C","分相电流差动保护+高頻距离保护；",true,{"key":23,"text":24,"correct":14},"D","短引线保护+断路器失灵保护。","分析：根据《继电保护和安全自动装置技术规程》（GB\u002FT14285—2006）中的关于主保护的规定“主保护是满足系统稳定和设备安全要求，能以最快速度有选择地切除被保护设备和线路故障的保护”，在上面所列的各种保护中，只有分相电流差动保护和髙频距离保护才能满足系统稳定的要求。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]