[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023454":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1023454,751,1,"单选题","某单端供电220kV电网如图14所示，AB线路A侧、BC线路B侧、BD线路B侧分别配置有三段式相间距离保护。 已知：可靠系数k=0.8,k'=0.8,k2=1时间级差△t=0.5，II段与相邻线路I段配合，灵敏系数km≥1.5，不考虑振荡闭锁和负荷电流的影响。 求：AB线路A侧相间距离保护I段的定值，即AB线路A侧、BC线路B侧、BD线路B侧距离保护的定值分别为（）Ω。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","8、16、12；",true,{"key":16,"text":17,"correct":18},"B","8、14、12；",false,{"key":20,"text":21,"correct":18},"C","8,16、14；",{"key":23,"text":24,"correct":18},"D","12、16、14。","计算距离保护I段的定值",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]