[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023416":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023416,751,1,"单选题","某煤电联营坑口火力发电厂，采用交流500kV电压等级、二回出线将电厂电力送到受端负荷中心变电所，送电线路长度（L）250km,每公里电容 （C）0.0126336 F，为限制工頻过电压和潜供电流要在每条500kV线路受端侧装设150Mvar髙压并联电抗器。请分析和计算以下问题。 —般情况下采用高、低压并联电抗器容量（QLΣ）为（）来补偿线路充电功率，才能符合《电力系统电压和无功电力技术导则》（SD325—1989）要求。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","420Mvar；",false,{"key":16,"text":17,"correct":14},"B","600Mvar；",{"key":19,"text":20,"correct":21},"C","540Mvar；",true,{"key":23,"text":24,"correct":14},"D","480Mvar。","QLΣ=QCΣX90%=600X90%=540（Mvar）",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]