[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023406":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023406,751,1,"单选题","某电力系统2010年丰水期最髙发电负荷20000MW，届时系统实际装机容量水电15000MW、火电10000MW、最大单机容量1000MW，负荷备用率取3%、事故备用率10%,经过电力平衡计算其工作容量由水电承担13000MW、火电承担7000MW。 水电站承担的事故备用容量是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1200MW；",false,{"key":16,"text":17,"correct":18},"B","1300MW；",true,{"key":20,"text":21,"correct":14},"C","800MW；",{"key":23,"text":24,"correct":14},"D","700MW。","在水、火电联合运行的电力系统中，事故备用一般按水、火电厂担负系统工作容量的比例分配，即 2000X13000\u002F2000=1300（MW）",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]