[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023358":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1023358,751,1,"单选题","某大型发电厂采用500kV电压等级，并经两回输电线路（线路主要数据：2X350km,LGJ-4X400mm2,每公里电抗为0.28Ω）向较强的受端电力系统送电，为了缩短输电线路的电气距离，以提高线路的输电能力和电力系统稳定性，根据规划论证决定在该输电工程中采用串联电容器补偿技术。 如不考虑其他因素影响，当串联电容器补偿度取50%时，串联电容器装置总容抗（Xc）是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","98Ω；",false,{"key":16,"text":17,"correct":18},"B","49Ω；",true,{"key":20,"text":21,"correct":14},"C","55Ω；",{"key":23,"text":24,"correct":14},"D","65Ω。","XL（线路电抗）=0.28X350=98（Ω） XC（串补容抗）=98X50%=49（Ω）",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]