[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023319":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023319,751,1,"单选题","送电线路与电信线路相对位置示意图如图15-2（电信线路系长途中继线、Ecd=1030V）,请按电信线路两端绝缘计算对地电压。 单相接地短路故障点在0点，D点对地电压为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","714V；",false,{"key":16,"text":17,"correct":14},"B","780V；",{"key":19,"text":20,"correct":21},"C","257.5V；",true,{"key":23,"text":24,"correct":14},"D","510V。","根据《输电线路对电信线路危险和干扰影响防护设计规程》（DI\u002FT5033-2006）的5.2.13条的有关规定及1款1》公式（5.2.13-1）。 已知：单相接地短路故障点在0点，电信线两端绝缘，Ecd=1O3OV,Lcd=15km,Lac=5km、Ldb=30km。 Ud=Ecd\u002F2（Lcd+2Lac）\u002F（Lcd+Lac+Ldb） =1030\u002F2（15+2X5）\u002F50=257.5（V） 接近段Uc+Ud=1030V=Ecd,计算正确。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]